TX700S
EN
Quick Start Guide
HMI – TX700S
Additional documents
Besides this document the following material can be found on the Internet at
www.turck.com:
Data sheet
Instructions for use for TX... series
Declarations of conformity (current version)
For your safety
Intended use
The IIoT edge controllers of the TX700 family are used to control, operate and
monitor machine processes.
The devices must only be used as described in these instructions.
Any other use is not in accordance with the intended use. Turck accepts no li-
ability for any resulting damage.
General safety notes
The device may only be assembled, installed, operated, parameterized and
maintained by professionally-trained personnel.
The device meets the EMC requirements for the industrial areas. When used
in residential areas, take measures to prevent radio frequency interference.
The device may only be used in accordance with applicable national and
international regulations, standards and laws.
Notes on explosion protection
Observe national and international regulations for explosion protection.
When operating the device in a hazardous area, the user must have a working
knowledge of explosion protection (IEC/EN 60079-14, etc.).
Only use the device within the permitted operating and ambient conditions
(see Certification data and conditions resulting from the Ex-approval).
This device is an open device and must be installed in a housing suitable for
the environment, so that the inner part of the device is only accessible by
means of a tool.
Do not disconnect devices in an ignitable atmosphere when energized.
Do not remove Ethernet connections, USB devices and SD cards in an ignit-
able atmosphere.
Do not open the device to remove the battery when energized.
Do not remove the battery in an ignitable atmosphere.
Switch-off the device before replacing or wiring extension modules.
Note on explosion protection (USA and Canada only)
The devices are suitable for the use in Class I, Division 2, groups A, B, C and D
(hazardous locations and non-hazardous locations).
The power, input and output (I/O) wiring has to be done in accordance with
Class I, Division 2 and in accordance with the authority having jurisdictions.
For U.S. in accordance with Article 501.10 (B) of the National Electrical Code,
NFPA 70 and for Canada in accordance with Section 18-1J2 of Canadian
Electrical Code.
Use only components that meet Class I, Division 2 certification.
Conditions resulting from Ex approval for use in Zone 2
Special conditions of use
The equipment shall only be used in an area of not more than pollution
degree 2, as defined in IEC/EN 60664-1.
The equipment shall be installed through an end-equipment enclosure
that provides a minimum ingress protection of IP54 in accordance with
EN IEC 60079-0, suitable for the applicable gas group, temperature classifica-
tion and ambient temperature range.
Transient protection shall be provided that is set at a level not exceeding
140 % of the peak rated voltage value at the supply terminals to the equip-
ment.
Observe the permissible ambient temperature depending on the tempera-
ture class.
Product description
Device overview
See fig. 1
Functions and operating modes
The IIoT edge controllers combine control, operation and monitoring by a
CODESYS V3 PLC with web visualization to a complete control unit. The
CODESYS V3 PLC of the TX700 devices has the functions PROFINET controller,
EtherCAT master, EtherNet/ IP scanner and Modbus TCP as well as Modbus RTU
client. Additionally the devices of the TX700 family can be used as PROFINET
device, Modbus TCP as well as Modbus RTU server.
Additional functions
Ethernet TCP/IP or UDP/IP communication
OPC-UA server and client, MQTT
Serial communication via RS232, RS485 and RS422
Installing
Mounting the device in Zone 2
DANGER
Explosive atmosphere
Explosion hazard due to ignitable sparks
For use in Zone 2
Only mount and connect the device if no explosive atmosphere is present.
Observe the conditions resulting from Ex approval for use in Zone 2.
Hook the device into the top-hat rail from below and tilt it upwards until the
upper snap-in hook engages on the DIN rail.
Do not cover the ventilation slots in the device.
Connection
Connectors and slots
See fig. 3
Connector/slot
Function
1
Serial interface
2
Power supply
3
Ethernet port 1 (10/100 Mbps)
4
Ethernet port 0 (10/100 Mbps)
5
USB ports, V2.0, max. 500 mA
6
Expansion slot for plug-in modules
7
SD card slot
NOTE
Devices of protection class III according to EN 61140 or Class 2 according to UL
standards:
All connections are SELV connections.
Power supply
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
Operate the device only on SELV voltage sources according to European
standard
or on Class 2 voltage sources according to UL standard
Connect the device to the voltage supply according to fig. 3 and 4.
Grounding the device
The device has to be grounded.
Ground the device via the grounding screw on the back of the housing or via
terminal 3 on the power supply terminal.
Observe the minimum cable cross-section of 1.5 mm² for the ground connec-
tion.
Serial interface
Connect serial devices according to fig. 5, fig. 6 or fig. 7.
NOTE
When used as RS485 interface, pins 1 and 2 as well as pins 3 and 4 must be
connected externally.