For JR8V individual series
W1
L1
Pipe
Branch
Indoor Unit
Select indoor main pipes and indoor branch B to J
The indoor units (N4 and N5) downstream of indoor
branch E have a total capacity of 7.1*2= 14.2kW.
Indoor main pipe L5 is Φ15.9 / Φ9.52. Indoor
branch joint E is EVRI-BP1.
The indoor units (N3 to N5) downstream of indoor
branch D have a total capacity of 14.2+7.1=21.3kW.
Indoor main pipe L4 is Φ19.1 / Φ9.52. Indoor
branch joint D is EVRI-BP1.
The indoor units (N2 to N5) downstream of indoor
branch C have a total capacity of 21.3+10=31.3kW.
Indoor main pipe L3 is Φ22.2 / Φ9.52. Indoor
branch joint C is EVRI-BP2.
The indoor units (N1 to N5) downstream of indoor
branch B have a total capacity of 31.3+10=41.3kW.
Indoor main pipe L2 is Φ28.6 / Φ12.7. Indoor
branch joint B is EVRI-BP3.
The indoor units (N10 and N11) downstream of
indoor branch J have a total capacity of 5.6+2.8= 8.4
kW. Indoor main pipe L10 is Φ15.9 / Φ9.52. Indoor
branch joint J is EVRI-BP1.
The indoor units (N9 to N11) downstream of indoor
branch I have a total capacity of 8.4+7.1= 15.5 kW.
Indoor main pipe L9 is Φ15.9 / Φ9.52. Indoor
branch joint I is EVRI-BP1.
The indoor units (N8 to N11) downstream of indoor
branch H have a total capacity of 15.5+10=25.5 kW.
Indoor main pipe L8 is Φ22.2 / Φ9.52. Indoor
branch joint H is EVRI-BP2.
The indoor units (N7 to N11) downstream of indoor
branch G have a total capacity of 25.5+11.2= 36.7
kW. Indoor main pipe L7 is Φ28.6 / Φ12.7. Indoor
branch joint G is EVRI-BP3.
The indoor units (N6 to N11) downstream of indoor
branch F have a total capacity of 36.7+11.2= 47.9
kW. Indoor main pipe L6 is Φ28.6 / Φ15.9. Indoor
branch joint F is EVRI-BP3.
L4
L3
L2
C
B
A
L6
b
a
N1(100)
N2(100)
F
L9
L8
L7
H
G
f
h
g
N6(112)
N8(100)
N7(112)
4.3.4
25
L5
E
D
e
d
c
N3(71)
N4(71)
N5(71)
L10
J
I
k
j
i
N9(71)
N10(56)
N11(28)
Select the indoor auxiliary connection pipe a to k
The capacity of indoor units N1 to N9 is larger than
5.6kW, so the indoor auxiliary connection pipe a to i
is Φ15.9/Φ9.52.
The capacity of indoor units N10 to N11 is equal or
less than 5.6kW, so the indoor auxiliary connection
pipe j to k isΦ12.7/Φ6.35.
Select main pipe (L1) and first indoor branch A
The system's equivalent length of all liquid pipes is
less than 90m, and the total capacity of the outdoor
units is 32HP. Main pipe L1 is Φ31.8/Φ19.1, first
Indoor branch A is EVRI-BP3.
Arrangement and layout of
multiple outdoor units
The piping between the outdoor units must be level
and lower than the outdoor unit piping connection.
Figure 4.10
V.1