7. Configuration and commissioning
Before starting control configuration, ensure that the pLAN connection terminals are disconnected.
Leaving the pLAN cable connected may cause the e-source components or the components it
NOTE
controls to malfunction or even break down.
If the software needs to be updated or the configuration needs to be deleted (installer menu →
default values) keep the pLAN cable disconnected.
Follow the configuration steps in the order shown in this section. Any change in the configuration
order may cause the unit to malfunction. If the configuration order is changed, delete the
configuration using the tool found in "installer menu → default values" and start again.
7.1. Software version and "default values"
Ensure that the e-source manager has the same software version number installed as the other controllers on the pLAN network.
The software version can be found in "user menu → information" (see point 0) and in "installer menu → information" (see point
6.6). The software version number is identified by the code Vxx_Bxxx (e.g. figure 7.1).
If necessary, update the e-source manager software or even the software of all the devices on the pLAN network. Make sure to
install the correct software for each device. As shown in figure 7.1, the e-source manager software is identified by the letters "SM",
the ecoGEO HP heat pump software by the letters "HP" and the supervisor module software by the letters "PS".
e-source
Figure 7.1. Example information screens showing the ecoSMART e-source, ecoGEO HP heat pump and ecoSMART Supervisor
Check that there is no configuration in the e-source electronic control. If there are any configuration parameters or if you are not
sure, delete the whole configuration using the tool in "installer menu → default values".
New password
1. Used to change the password to access the INSTALLER menu (PW1).
ecoGEO HP
software version.
61
ecoSMART e-source
user, installer and technical service manual
Supervisor