CAUTION
To protect yourself, think "Safety First":
• Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
• Use appropriate personal protective equipment such as safety glasses, face shields, insulating
gloves, insulating boots, and/or insulating mats.
• Never ground yourself when taking electrical measurements.
• Always work with a partner.
• When using the probes, keep fingers as far behind the probe tips as possible.
Operating Instructions
• Before proceeding with mea-
surement, if the
"
" symbol appears on the
display, replace with new batter-
ies.
• Short the tips of the leads.
Adjust the 0Ω. ADJ control to
set the reading to zero.
• Rotate the function switch to the "EARTH VOLTAGE" position and press to test. Earth
voltage will be displayed on the LCD. If earth voltage is more than 10V, an inaccurate reading
may be obtained.
• Precision earth resistance measurement method:
(1) Connect the green, yellow and red test leads to instrument terminals E, P and C with
auxiliary earth spikes P1, C1 placed into the soil "IN A STRAIGHT LINE". (Fig. 1)
(2) Rotate the function switch to a suitable range then press the pushbutton to test and
take the reading.
•
Simplified earth resistance measurement method
(1) This method is recommended where an earth resistance higher than 10Ω is
measured or where it is not possible to drive auxiliary earth spikes. An approximate
value of earth resistance can be obtained by the two wire system shown in Fig. 2.
(2) Rotate the function switch to "EARTH VOLTAGE" position and press to test. Make
certain that earth voltage is less than 10V.
(3) First rotate the function switch to the "200Ω" position and press to test. Read earth
resistance. If the display shows "1" (MSD), switch to the "2KΩ" position and read
earth resistance.
(4) The reading obtained (Rx) is an
approximate earth resistance
value. There is no need for
external shorting as P and C
terminals are shorted by
using the test leads
specified for the simplified
measurement.
Red
Yellow
Auxiliary
Earth Spikes
100'
Green
Red
C
E
P
2
Figure 1
E
Green
63'
Ground Rod
Secondary
Side
re
Rx
Earth
Electrode
under test
Where earth for mains power
supply is used.
C
P
Figure 2
Rx = Re-re
Primary
Side
Supply
Transformer