Use this receptacle to operate 240 Volt AC, 60 Hz, single
phase loads requiring up to 8,000 watts (8.0 kW) of power.
The outlet is protected by a 35 Amp push–to–reset circuit
breaker.
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 6).You can use the same 4–wire cord if you
plan to run a 120 Volt load.
Figure 6 — 120/240 Volt AC, 30 Amp Receptacle
4-Wire Cord Set
Y (Hot)
NEMA L14-30
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts of power at
30 Amps for 120 Volts; 7,200 watts of power (7.2 kW) at
30 Amps for 240 Volts.The outlet is protected by a 30 Amp
push–to–reset circuit breaker.
120 Volt AC, 30 Amp Locking
Receptacle
Use a NEMA L5–30 plug with this receptacle. Connect a
3–wire cord set rated for 125 Volt AC loads at 30 Amps to
the plug (Figure 7).
PowerBoss 8,000 Watt PowerMaster Generator
240V
120V
120V
W (Neutral)
X (Hot)
Ground (Green)
Figure 7 — 120 Volt AC, 30 Amp, Locking Receptacle
3-Wire Cord Set
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts (3.6 kW) of power
at 30 Amps.The outlet is protected by a 30 Amp
push–to–reset circuit breaker.
120 Volt AC, 20 Amp, Duplex
Receptacle
Each receptacle (Figure 8) is protected against overload by
a 20 Amp push–to–reset circuit breaker.
Figure 8 — 120 Volt AC, 20 Amp, Duplex Receptacle
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).
10
NEMA L5-30
Neutral
120V
Hot
Ground (Green)