DIG 2 PULSE CLOSEOPEN counts the pulses on closedopen variation of input 2
• Time meter management
The device can be queried to know the value of the time meter or to reset it with the
command:
TIMER [[input number][function]
− [input number]
− [function]
Some examples:
TIMER 2 READ reads the status of the time meter associated to input 2
TIMER 1 RESET resets the time meter associated to input 1
• Time meter alarm setting
When a time meter threshold value is reached it is possible send a text message or a
ring to the contact numbers
TIMERALARM [input number][count][time unit of measurement][automatic reset]
− [input number]
− [count]
− [time unit of measurement] s seconds, m minutes, h hourse
− [automatic reset]
Some examples:
TIMERALARM 1 10 H AUTORESET sends a text message of alarm when the count on
TIMERALARM 2 30 M sends a text message of alarm when the count on input 2
• Pulse meter management
The device can be queried to know the value of the pulse meter or to reset it with the
command:
PULSE [input number][function]
indicates which digital input (1 or 2)
READ reads the count, RESET resets the count
indicates which digital input (1 or 2)
indicates the count value that must trigger the alarm
(max 2
-1 s) (0 disable alarm)
32
AUTORESET to reset the time meter automatically upon
reaching the threshold (optional parameter)
input 1 reaches 10 hours and resets the meter
reaches 30 minutes (it does not reset the meter)
- 45 -