ALARM MANAGEMENT

Using command SENDALARM you define who (of the STAFF numbers) to send the alarms
and in which format (SMS or RING))
SENDALARM [type of alarm][recipient[type of signalling]...[recipient][type of signalling]
[type of alarm]
[recipient]
[type of signalling]
Some examples:
SENDALARM DIG1 1 SMS 2 RING 3 RING  when there is an alarm on digital input 1,
SENDALARM RMAX 2 SMS 6 RING  when there is a return of the maximum threshold
SENDALARM with [alarm type] displays the alarm warning parameters for the type of
selected alarm
Example: by sending the command SENDALARM DIG1 the device responds with
DIG1=1M,2R,-,-,-,-,-,-,-,-, which means: send SMS to STAFF 1 and RING to STAFF 2 if
there is an alarm on Digital 1
NB: a new SENDALARM setting overwrites the previous, so it is necessary to
show all the recipients of the alarms in one sole command.
NB: to cancel a SENDALARM setting, enter '0' as the recipient.
Example:
SENDALARM DIG1 0  cancels the sendalarm settings for DIG1  DIG1=-,-,-,-,-,-,-,-,-,-,
The alarm sources are the following:
Table 1
Type of alarm
Alarm description
DIG1
Alarm from digital input1
RDIG1
Alarm return from digital input1
DIG2
Alarm from digital input2
RDIG2
Alarm return from digital input2
MIN
Minimum alarm from analogue input
RMIN
Minimum alarm restore from analogue input
see table 1, pag. 51
STAFF number index
[SMS, RING]
it sends an sms to contact 1 and a ring to
contacts 2 and 3
it sends an alarm sms to contract 2 and a ring to
contact 6
- 51 -
User Manual CODITEL 2