Samlex Europe PST-300S-12E Manual Del Propietário página 35

Tabla de contenido

Publicidad

against short circuit. Amp rating of the fuse is based on the following considerations:
a) Not less than the Maximum Continuous DC Input Current (Column 2)
SECTION 8 |
b) C losest Standard Ampere Rating of fuse has been used - Refer to NEC-2014
(National Electrical Code) - Section 240.6(A)
c) W here Standard fuse Rating does not match the required Ampacity (Col-
8.4.5 Recommended Sizes of Battery Cables and Fuses
umn 2), the next higher Standard Rating of the fuse has been used - Refer to
Sizes of cables and fuses are shown in Table 8.2. Sizing is based on safety considerations
NEC-2014 (National Electrical Code) - Section 240.4(B)
in UL-458, NEC-2014 and ISo -10133. Please refer to "Notes for Table 8.2" for
d) type of fuse: fast-acting, Current Limiting, UL Class T (UL Standard 248-15)
details.
or equivalent
5) S amlex America, Inc. makes 4 Models of generic / universal Inverter Installation Kits to cov-
Table 8.2 Recommended Sizing of Battery Cables
er installation requirements of a wide power range from 600W to 3500W for 12V invert-
and External Battery Side Fuse
ers and from 1200W to 7000W for 24V inverters. Please note that the Inverter Installation
Model No.
Maximum
Kit that has been recommended in Column (8) may include thicker wire size / correspond-
Continu-
ingly bigger fuse size than those recommended in Table 8.2. This is acceptable.
ous DC
Input
fuse in the battery circuit is primarily required for protection against short circuit in
Current
the battery cable run. The size of this fuse has to be equal to or larger than the maxi-
mum DC input current of the inverter at Column (2). further, the Amp rating of the
fuse used for protecting a battery cable against short circuit has to be lower than the
Ampacity of the cable so that the fuse blows before the cable insulation is damaged
due to overheating as a result of fault current higher than the Ampacity of the cable.
The Amp ratings of fuses provided with the Inverter Installation Kits are lower than
the wire size provided with the Kit.
PST-300S-12E
360A
The Kits come with 10ft length of cables to cover battery to inverter distance of up to
PST-300S-24E
180A
10 ft. If the actual cable routing distance from the battery to the inverter is less than
10ft, please cut-off the extra length of cables. This will result in reduction in the over-
all resistance of the cable / reduction in voltage drop and consequently, will improve
the efficiency of the inverter system
8.4.6 Dc input connection
The DC input terminals for battery connection (14 & 16 in fig. 6.1c) have nut and bolt con-
nection - bolt size is 5/16" (18 Threads per Inch). Use ring tongue type of terminals on the
wire ends to fit 5/16" bolt size.
8.4.7 Reducing RF interference
Please comply with recommendations given in Section 3 - "Limiting Electromagnetic
Interference".
36 | SAMLEX AMERICA INC.
Installation
Maximum
Minimum cable size
External
(See Note 4)
Battery
< 1,50 mm
Fuse Size
400-500A
95
300A
50
2
> 1,6-3 mm
2
120
70
SAMLEX AMERICA INC. | 35
35
35

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pst-300s-24e

Tabla de contenido