WEG CFW700 Manual Del Usuario página 39

Ocultar thumbs Ver también para CFW700:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Keypad (HMI) and Basic Programming
P1012 – PID Feedback
Adjustable
0.0 to 3000.0
Range:
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Read only parameter that presents, in the wxy.z form without engineering unit, the feedback
value or the process variable of the PID regulator according to the scale defined at P1018.
P1013 – PID Output
Adjustable
0.0 to 100.0 %
Range:
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Read only parameter that presents, in percentage (%), the PID regulator output value.
P1016 – PID Setpoint Selection
Adjustable
0 = HMI
Range:
1 = AIx
2 = Serial/USB
3 = CO/DN/DP
Properties:
ro
Access Groups
SPLC
via HMI:
Description:
Defines the source of the PID regulator setpoint.
Notes:
"HMI" means that the PID regulator setpoint will be the value of P1025 parameter.
"AI" means that the PID regulator setpoint will come from an analog input. It is necessary
to set P0231 (AI1) or P0236 (AI2) to 5 = Function 1 of the Application in order to enable its
operation. The following alarm message will be displayed in case it is not properly done:
"A770: Set AI1 or AI2 for Function 1 of the Application".
"Serial/USB" means that the setpoint of the PID will be the value of P0683 proportionally
referenced to the percentage value with one decimal point, i.e., 100.0 % corresponds to
1000 in P0683.
34 | CFW700
Factory
-
Setting:
Factory
-
Setting:
Factory
0
Setting:

Publicidad

Tabla de contenido
loading

Tabla de contenido