5. PROGRAMMATION
5.2 Application cosφ
OFF EXCLUT L'ATTENTE
REMPLISSAGE
ATTENTE REMPLIS.
OFF
IL SERT À FIXER UN TEMPS
D'ATTENTE REMPLISSANGE QUI
INTERVIENT CHAQUE FOIS QUE LA
CARTE MÉRE DÉTECTE UN
ÉTAT DE MARCHE À SEC
RANGE 1min ÷ 99h 59min
ATTENTE REMPLIS.
0 h 30 min
ATTENTE REMPLIS.
5.1
0 h 30 min
EN MODE OFF, LA CARTE MÈRE
EXCLUT LE CONTRÔLE SUR
LA COMMANDE EXTERNE
COMMANDE EXTERNE
0FF
EN MODE 2 ENTRÉES LA COMMANDE
EXTERNE EST:
OFF G.MIN E G.MAX FERMEES (DÉSACTIVE MOTEUR)
ON G.MIN E G.MAX OUVERTES (ACTIVE MOTEUR)
COMMANDE EXTERNE
2 ENTREES
EN MODE 1 ENTRÉE LA
COMMANDE EXTERNE EST:
OFF G.MIN OUVERT (DÉSACTIVE MOTEUR)
ON G.MIN FERMÉ (ACTIVE MOTEUR)
COMMANDE EXTERNE
1 ENTREE
COMMANDE EXTERNE
1 ENTREE
IL SERT À RÉGLER MANUELLEMENT
LA VALEUR DU COSF SOUS LA QUELLE
LA POMPE TOURNE À SEC
RANGE 0.04 ÷ 0.99
COSFI MINIMAL
MAN.
0.68
MAN. INDIQUE QUE LA VALEUR
DU COURANT MINIMAL
A ÉTÉ DÉFINIE MANUELLEMENT
COSFI MINIMAL
AUT.
0.68
AUT. INDIQUE QUE LA VALEUR DU COSFφ
A ÉTÉ DÉFINIE AVEC L'AUTO-APPRENTISSAGE
9
IL PERMET DE RÉGLER
LE DÉLAI D'INTERVENTION
SUR L A PROTECTION
DE LA MARCE À SEC
RANGE 1 ÷ 10s
DELAI COSFI
MINIMAL
DELAI COSFI
MINIMAL
PRESSEZ POUR VOIR LA PARTIE RESTANTE DE
PARAMÈTRES VOIR CHAPITRE 5.5
PRESSEZ POUR PLUS DE 1S POUR QUITTER
LE SETUP ET ENREGISTRER LES PARAMÈTRES
DANS LA MÉMOIRE
FRANCAISE
4 s
4 s