9- Installing batteries

insert the battery charging circuit in the battery card connector and connect the batteries to the circuit, with battery operation the speed of the motor is 15%
lower than the speed with mains power, the number of operations with the batteries depends on the number of photocells in the system and the length of the
gate.

10-Troubleshooting:

Problem
The automatic gate system does not work
You cannot save the remote controls
The remote control does not work
You cannot enter travel programming
As soon as the gate starts it stops and re-
verses
During slowdown, the gate stops and reverses
The gate does not stop with the limit
switches tripping

11-Programmable parameters:

Table summarizing the parameters changed during installation
Parameter number
44 44
Cause
No mains supply
Blown fuses
Control and safety inputs not working
Safety devices open
Batteries of the remote control discharged
Remote control not compatible with the first one saved
Reached memory saturation
Batteries of the remote control discharged
Safety devices open
Low acceleration on starting
Slowdown speed too low
The magnetic sensor cannot read the magnet
Solution
Check the power line switch
Replace the fuses with others of the same value
Check the diagnosis LEDS (STOP, STPA and
PHOTO must be on)
Check the diagnosis LEDs (STOP, STPA and
PHOTO must be on)
Replace the batteries
The first saved remote control configures the con-
trol panel to save only rolling-code remote controls
or only dip-switch remote controls
Delete at least one remote control or add an ex-
ternal receiver (maximum capacity 200 remote
controls)
Replace the batteries
Check the diagnosis LEDS (STOP, STPA and
PHOTO. must be on)
Decrease the value of parameter 24
Check the encoder connector is inserted (during
gate movement the enc a and enc b LEDs must
be on)
Increase the value of (parameter 13 and 14) or de-
celeration too fast (parameter 25)
Move the magnet near to the sensor
Check the LEDs of the limit switches.
Magnet direction incorrect, check the SW.CL LED
that should turn off when the gate is fully closed,
check the SW.OP LED that should turn off when
the gate is fully open
Value