CUS100ME Handbook
Environmental Specifications:
Description
Use
Temperature
Humidity
Altitude
Pressure
Orientation
Material Group
Pollution Degree
Overvoltage Category
Description
Class
Weight
IP Rating
WARNING: No modification of this product is allowed.
Level of Insulation:
Dielectric Strength type testing is carried out as follows:
Primary mains circuit to earth: 2.5 kVdc.
Primary mains circuits to secondary: 6.25 kVdc
Secondary circuits to earth: 2.5 kVdc.
Safety Approvals:
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC/EN60950-1 – CE mark.
CE marking when applied to any CUS100ME product, indicates compliance with the Low Voltage Directive
in that it complies with EN62368-1 and with the RoHS Directive.
UL/CSA 60601-1/ANSI/AAMI ES 60601-1 - UL + C -UL approval
IEC/EN/UL 62368-1
Fusing:
Internal Dual fuses (F1 and F2) in the live and Neutral line, T3.15AH, 250V. (Standard CUS100ME)
Internal Single fuse (F1) in the live line, T3.15AH, 250V. (Option /E)
Symbols:
AC
EARTH
Caution: See instructions for use
Operation
Indoor
-20°C to 85°C (Model dependent. See o/p tables for
de-ratings)
5 to 95% RH, non-condensing
-200m to 5000m
70kPa to 106kPa
Any excluding inverted.
N
Neutral
Live
Page 14 of 24
IIIb
2
II
I and II
Typical 180g (open frame)
IPX0
L
Warning: Dangerous Voltage
Storage
-
-40°C to 85°C
5 - 95% RH, non-condensing
-200m to 5000m
54kPa to 106kPa
All
260423-3 Mar 2019