Earth Resistance Clamp Meter

2.Earth resistance measurement

1. After switching on, the instrument is automatism in
measurement current mode, you can press the▼Ω
button to configure for resistance measurement mode.
2. Hook the clamp jaw around earth leads or electrode
to be tested.
3. If symbol " - - - " and
symbol are shown on the
display, it indicates that the clamp is closed incompletely.
You must press the trigger of the instrument several
times to close the clamp jaw correctly. After the
symbol disappears from the display, then it is in the
normal measurement mode.
4. Read the measurement value on the display.
5. When the display appears the "NOISE" symbol, it
indicates that there is an interference current in the
loop, the resistance measurement is not assured.
6. Schematic of measurement
• Buzzer ON
• Aloop earth resistance of 36.2Ω
• The batteries service life is 87%
35
07
Earth Resistance Clamp Meter
• Buzzer ON
• A loop earth resistance of 68.7Ω
• The earth resistance value is above the high
alarm threshold 50Ω, a beep is emitted
• Buzzer ON
• A loop earth resistance of 0.5Ω
• The earth resistance value is less than the low
alarm threshold value 8Ω, a beep is emitted
36
08