Switching And Make-Up Variants - Reflex Servitec S Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 537
Proceed as follows:
Connect the "DC" degassing lines in the "V" main volume flow of the facility system.
The device requires two "DC" degassing lines to the facility system.
One degassing line for the gas-rich water from the facility system
One degassing line for the degassed water back to the facility system.
Fit the degassing lines near the "EC" expansion line.
This ensures stable pressure conditions.
Install the device near the "MAG" expansion vessel.
This ensures pressure monitoring of the expansion vessel.
Set the "Magcontrol" operating mode at the device controller.
Note!
Ensure the integration with the "V" main flow volume. in particular in switching variants with hydraulic
switching points and return admixtures.
For switching and make-up variants, see chapter 6.4 "Switching and make-up variants" on page 15 .
6.3.3.1
Make-up line
1
"ST" dirt trap
2
"BT" system separator vessel
3
"WC" make-up line
4
Device
5
"DC" degassing line (gas-rich water)
6
"DC" degassing line (degassed water)
For water make-up, note the following conditions:
For a water make-up via a "BT" mains disconnect
receptacle, its bottom edge must be at least 1 m over
the "PU" device pump.
Close the connection of the "WC" make-up line when a
make-up line is not connected.
Adjust the "Levelcontrol" make-up variant at the
device controller.
Install at least one "ST" dirt trap with a mesh size ≤ 0.25 mm close upstream to the "CD" 2-ways motorized ball valve.
Note!
Avoid a device fault.
Ensure that manual water make-up to the facility system is possible.
Note!
Use a pressure reducer in the "WC" make-up line if the idle pressure exceeds 6 bar.
6.4

Switching and make-up variants

The device has two make-up variants:
Pressure-dependent "Magcontrol" make-up.
In a facility system with an expansion vessel.
Level-dependent "Levelcontrol" make-up.
In a facility system with a pressure maintenance station.
As supplied, the device is preset to "Levelcontrol" operating mode. If no pressure maintenance station is connected,
pressure-independent degassing takes place without automatic make-up, see chapter 7.4 "Starting Automatic mode"
on page 21 .
Vacuum spray degassing — 20.05.2019
Installation
English — 15

Publicidad

Tabla de contenido
loading

Tabla de contenido