7.3
Filling the device with water
Use the system to fill water into the device.
•
Open the ball valve and the motorized ball valve of the
make-up pipe to the system.
7.4
Starting Automatic mode
Automatic mode can be started as soon as the system is filled with water and the gases contained have been vented.
•
Press "Auto" on the controller's operator panel.
A vacuum test is performed automatically during initial commissioning and after a reset. In doing so, both motorized ball valves are
closed and the pump switched on. A vacuum must be built up during the pumping time and then must not decrease by more than
0.1 bar inside 50 s.
After the vacuum test has been passed, automatic mode can be started.
During commissioning, continuous degassing is automatically activated to remove any residual free or dissolved gases from the
system. The times for continuous and interval degassing can be set in the customer menu of the Reflex Control Smart app
dependent on the system conditions. The default setting is 24 hours. Subsequent to the continuous degassing, the device
automatically switches to interval degassing.
Operation without Reflex Control Smart
The preset default values are the following:
•
Continuous degassing for the first start (24 hours constant degassing).
•
Thereafter the system switches over to interval degassing (10 cycles per day).
Note!
Continuous degassing can be interrupted by pressing the "stop-button" and then switched back on using the "Auto"
button. The Servitec S is now operating in interval degassing mode (10 degassing cycles every 12 hours).
The start of interval degassing is automatically based on the time of initial commissioning. For example, if continuous
degassing started at 15:00, interval degassing would commence after 24 hours with 10 cycles.
Note!
The commissioning process is now concluded.
Notice!
The "ST" dirt trap in the "DC" degassing line must be cleaned after the expiry of the continuous degassing time at the
latest, see chapter 10.2 "Cleaning the dirt trap" on page 27 .
8
Operation
8.1
Operating modes
8.1.1
Automatic mode
Automatic mode includes the two operating modes continuous degassing and interval degassing.
Note!
The starting time of the degassing processes is specified based on the time at the very first start.
•
To reset and for new setting of the start times, see chapter 9.5 "Reset" on page 25
Vacuum spray degassing — 20.05.2019
Operation