A function to exclude all modification to operating parameters can be enabled; measure-
ment viewing is still provided in any case.
To lock and unlock the keypad, press and keep
key three times and the
The display will show LOC when the keypad is locked and UNL when it is unlocked.
When the lock is enabled, it is not possible to make the following operations:
Operation between automatic and manual mode
Access to set-up menus
Change of cosø set-point
By attempting to conduct the above operations, the display will view LOC to indicate the
locked keypad state.
Thanks to expansion bus, the PFC96evo can be expanded with one expansion series module.
The supported expansion modules can be grouped in the following categories:
additional steps
communication modules
digital I/O modules
To insert an expansion module:
remove the power supply to PFC96evo regulator.
remove the protecting cover of the expansion slot.
insert the upper hook of the expansion module into the fixing hole on the top of the
expansion slot.
rotate down the module body, inserting the connector on the bus.
push until the bottom clip snaps into its housing.
Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: italfarad@italfarad.com Web: www.italfarad.com
Keypad lock
key twice and after that release
Expandability
ITALFARAD S.p.A. via IV novembre n.1 Minerbio Bo Italy
key pressed. Then press the
E