COD
DESCRIPTION
P.21
Password enable
P.22
User password
E
P.23
Advanced password
N
P.24
Wiring type
P.25
Step trimming
P.26
Setpoint clearance +
P.27
Setpoint clearance -
P.28
Step insertion mode
P.29
Cogeneration cosø setpoint
Disconnection
P.30
sensitivity
P.31
Step disconnection passing in MAN
Capacitor current overload alarm
P.32
threshold
Capacitor overload immediate
P.33
disconnection threshold
P.34
VT primary
P.35
VT secondary
P.36
Temperature UoM
P.37
Fan start temperature
P.38
Fan stop temperature
P.39
Temperature alarm threshold
P.41
Maximum voltage alarm threshold
P.42
Minimum voltage alarm threshold
P.43
THD V alarm threshold
P.44
THD I alarm threshold
Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: italfarad@italfarad.com Web: www.italfarad.com
Advanced menu
PSW UoM
Adv
Usr
Adv
Usr
Usr
Usr
Usr
Usr
Usr
Usr
Usr
Adv
Adv
Usr
Usr
Usr
Adv
Adv
Adv
Adv
Adv
Adv
Adv
ITALFARAD S.p.A. via IV novembre n.1 Minerbio Bo Italy
DEF
RANGE
OFF
OFF
ON
001
0-999
002 (*)
0-999
3PH three-phase
3PH
1PH single-phase
ON Enabled
ON
OFF Disabled
0.00
0 – 0.10
0.00
0 – 0.10
STD Standard
STD
LIN Linear
OFF /
OFF
0.50 IND – 0.50 CAP
sec
OFF
OFF / 1 – 600
OFF
OFF Disabled ; ON Enabled
%
50
OFF / 0...150
%
83
OFF / 0.. 200
V
OFF
OFF / 50-50000
V
100
50-500
°C
°C °Celsius ; °F °Fahrenheit
°
25
0 .. 100°C ; (32...212°F)
°
20
0 .. 100°C ; (32...212°F)
°
55
50 .. 100°C ; (122...212°F)
%
110
OFF / 90...150
%
90
OFF / 60..110
%
6
OFF / 1..250
%
12
OFF / 1..250
50