LANDIS LMO 44 CONTROL INFORMATION SYSTEM
In case of burner lockout, it is possible to read which cause originated it. Proceed as follows: with the burner in lockout
mode (red LED switched on) keep pressed the lockout button for more than 3 sec. then release it. The red LED will
blink according to the following error code list:
Error Code
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
Possible cause
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner,
no fuel - Faulty ignition
Free
Extraneous light on burner start-up
Free
Free
Too many losses of flame during operation (limitation of the number of repetitions)
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner
Time supervision oil pre-heater
Free
Wiring error or internal error, output contacts
FIRING HEAD SETTING
420010362200 Maior P 300.1/400.1 AB
17