BIP LD2-T017-04-BP _ _ / BP _ _ -S4
Inductive Positioning System
6
IO-Link interface (continued)
6.10

Switching state

The operating mode Single Point Mode was implemented
for the switching channels BDC1...BDC3.
If the position value exceeds the switching threshold, the
switching signal changes. The switch-off point lies above it
by the hysteresis value and the switching threshold is
defined with setpoint 1.
Switching behavior with hysteresis is described in Fig. 6-1.
Hysteresis
BDC
ON
SP1
Hysteresis
BDC
OFF
SP1
Fig. 6-1:
Hysteresis switching behavior with setpoint 1 (SP1)
6.11
Teaching in the switching channels with
a target
Position the target at the desired range, select switching
channel, and save switching position.
If the target leaves the measuring range during
teach-in, the error message
TEACH_STATE_ERROR is shown.
Perform teach-in
1. Select switching channel.
2. Move the target to the desired position.
3. Temporarily save current position as switchpoint.
4. Check the teach-in status register (as required).
5. Apply and activate switchpoint function.
See Tab. 6-11 on page 16, hexadecimal value
1)
www.balluff.com
OFF
Measured value
ON
Measured value
Setpoint1
The SP1 switching threshold value saves the output value
at which switching should take place.
Value range 0x0014...0x0FEB (20
Switchpoint logic
Logical switching state:
0: NO (normally open)
1: NC (normally closed)
Switchpoint hysteresis
Switchpoint hysteresis with value range 0x0013...0x0FEA
(19
...4074
).
10
10
Switchpoint mode
(Switchpoint operating mode)
All switching channels are initially deactivated. After
entering the switching channel parameters, each switching
channel must be explicitly enabled.
0: Lock switching threshold function
1: Enable switching threshold function
Index
Subindex
Hex.
Dec. Hex. Dec.
003A
58
00
0
0002
2
00
0
003B
59
00
0
0002
2
00
0
...4075
).
10
10
Access
Value
Write only
Channel number
Write only
0x41
Read only
0x14
Write only
0x40
english
1)
15