Start-Up; Maintenance - Lamborghini Caloreclima Reply 51 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Reply 51 - 71 - 101

3.2 Start-up

B
Checks to be made at first lighting, and after all maintenance operations that involved disconnection from the
systems or an operation on safety devices or parts of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap and water solution to detect any
leaks in connections.
Check correct prefilling of the expansion tank (ref. sec. 4.4).
Fill the water system and make sure all air contained in the boiler and the system has been vented, by opening the
air vent valve on the boiler and any vent valves on the system.
Fill the condensate trap and check correct connection of the condensate elimination system.
Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
Check correct connection of the electrical system and efficiency of the earthing system
Make sure the gas pressure value for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler
Checks during operation
Turn the unit on as described in sec. 1.3.
Make sure the fuel circuit and water systems are tight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check the correct tightness and functionality of the condensate elimination system and trap.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water production phases.
Check proper boiler lighting by doing several tests, turning it on and off with the room thermostat or remote control.
Using a combustion analyser connected to the boiler fume outlet, check that the CO
boiler operating at max. and min. output, corresponds to that given in the technical data table for the corresponding
type of gas.
Make sure the fuel consumption indicated on the meter matches that given in the technical data table on sec. 4.4.
Check the correct programming of the parameters and carry out any necessary customization (compensation curve,
power, temperatures, etc.).

3.3 Maintenance

Periodical check
To keep the unit working properly over time, it is necessary to have qualified personnel make an annual check that in-
cludes the following tests:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must function correctly.
The fume extraction circuit must be fully efficient.
The airtight chamber must be sealed
The air-fume end piece and ducts must be free of obstructions and leaks
The condensate evacuation system must be efficient with no leakage or obstructions.
The burner and exchanger must be clean and free of scale. When cleaning, do not use chemical products or wire
brushes.
The electrode must be free of scale and properly positioned.
The gas and water systems must be airtight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring it to that value.
The circulation pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables.
A
The boiler casing, panel and aesthetic parts can be cleaned with a soft damp cloth, possibly soaked in soapy
water. Do not use any abrasive detergents and solvents.
EN
cod. 3540H322 - 09/2008 (Rev. 01)
content in the fumes, with the
2
85

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Reply 71Reply 101

Tabla de contenido