Xylem CentriPro AQUAVAR SOLO2 Manual De Instalación página 12

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Press and Hold MODE
button for 5 seconds

(Dry Well Settings)
DOWN

MODE
(Sensor Zero)
NOTE: Ensure the transducer is exposed to 0 PSI
before performing the Sensor Zero function. To
DOWN
exit , press both UP and DOWN buttons.

MODE
(Fault History Reset)
DOWN

(Sensor Range Select)
DOWN

MODE
(Relay Configuration)
DOWN
DRY WELL SETTINGS - dSE
The Dry Well function is used to protect the pump against
damage caused by situations such as running dry, running
against at no flow or running while air bound. Use the dSE
menu to configure this function.
O – Disable. This selection will disable the Dry Well
function. If selected there will be no protection against
damage to the pump from a dry well condition. Make
this selection only if the pump will never run out of
water, break suction, run against a closed valve or
become plugged.
P – Progressive Restart. This selection controls the
restart feature of the Dry Well function. When selected,
the controller will automatically reset the Dry Well
Fault (02, 2 blinks) according to the Progressive Reset
schedule. This is the default setting for the dSE menu.
12
MODE


MODE

(Run)
DOWN

(Fault)
DOWN

(NOT Fault)
DOWN

(Disable)
DOWN

(Progressive)
DOWN

(Never Restart)
DOWN

MODE
(Fixed Time Restart)
DOWN

DOWN

DOWN

DOWN
PROGRESSIVE RESET SCHEDULE
Number of Dry Well
Faults Detected
1
2
3
4
5 and greater
S – Never Restart. This selection disables the restart
feature of the Dry Well function. When selected, the
controller will never reset if a Dry Well Fault (02, 2 blinks)
is detected. If this setting is selected the Dry Well fault
can only be reset by powering down the controller or by
pressing the UP and DOWN buttons at the same time.
 – Fixed Time Restart. This selection allows the user to
select a fixed time between detection of a Dry Well fault and
an automatic restart. This function will continue to reset the
Dry Well fault and restart the controller after the specified
10-50 min in 10 min increments
1-48hr in 1 hr increments
Reset Time
1 minute
10 minutes
20 minutes
30 minutes
60 minutes