Troubleshooting

The ProNauticP includes advanced fault indication. Faults, if indicated, may require service
from ProMariner. For inquiries and service information Please call our Customer Care
Department line at 1-800-824-0524 from 8:30 am to 5 pm (Eastern Standard Time) for
any warranty, service or installation assistance you may need. Thank You
! THERE ARE NO USER SERVICEABLE PARTS INSIDE THE PRONAUTICP. DO NOT
ATTEMPT TO DISSASEMBLE THE UNIT. EVIDENCE OF DISSASEMBLY WILL VOID
MANUFACTURERS WARRANTY.
The first step to any problem is resetting the ProNauticP unit by turning off the AC breaker
providing power, waiting at least 10 seconds and turning it back on again.
Review the Operations section for the meaning of the fault indicator and suggestions on how
to clear the fault.
Charger Fault (Service) Conditions
LED Label
LED Color
Reverse Polarity
Red
Check DC Connections, ensure positive + (RED) and negative - (BLACK and/or YELLOW)
connections are attached accordingly
DC Volts Low
Amber
Bring system voltage over 11.0 VDC, check battery(s) condition and replace as necessary.
DC Volts High
Red
Using a multi-meter check alternator(s) output, generally over 15VDC. Determine if fault exists
in regulator or alternator, solar panel, wind generator etc. Replace as needed.
Charger High Temp Amber
Generally this indicates that the unit has been installed in an area with a very high ambient temperature. This
unit is designed for use in an engine room, if installed in an engine compartment; ensure that there is proper
ventilation in the space for the charger and other temperature sensitive components. If the installation area
temperature is 45° C (113° F) or more, move charger or add ventilation to lower ambient temperature. The
recommended maximum ambient temperature for installation is 45° C. (113° F)
Check Fan
Red
Ensure that the cooling fan can move freely and that no debris is blocking the fan movement.
Persistent fan problems require service from ProMariner.
Fault
Red
Please contact ProMariner for service options.
Auto Temp Control Red flashing
See charger high temp above
Note: Installation is permitted in an environment of 45° C (113° F) and may result in output
of unit decreasing to protect the internal components and the performance of the unit.
Fault
Indicates a reverse polarity situation
DC system voltage is less than 11.0 VDC
Indicates a high DC voltage from an outside source
such as a failed alternator
Charger has shut down due to high temperature
Fan failure
Indicates a fault
High temp causes unit shutdown