2.6.3.

DC Output

ELK model
OP1
OP2
+
+
7
9
-
-
8
10
Not isolated from the sensor input
Software configurable: 0-20mA or 4-20mA.
Max load resistance: 500Ω
Cal. accuracy: +(<1% of reading + <100µA)
Output functions: Heating, or cooling, or
retransmission.
16
ETK model
OP1
OP2
+
+
15
13
16
14
-
-
2.6.4.

Logic Contact Closure Input (I/O1 only)

ELK model
OP1
7
8
Not isolated from the sensor input
Switching: 12Vdc at 40mA max
Contact open > 500Ω. Contact closed < 150Ω
Input functions: Please refer to the list in the Quick
Start codes.
Part number HA028438. Issue 3.0.
ETK model
OP1
13
14