12 EN – Quick installation and start-up guide
Default I/O connections
Default I/O connections of the ABB Standard macro are shown below.
ABB standard macro:
1...10 kohm
EN
DA
max.
500 ohm
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
S1
AI1 U/I
S2
AI2 U/I
XIA
Signal cable shield and analog input 1
1
SCR
2
AI1
3
AGND
XIB
Reference voltage and analog input 2
4
+10V
5
AI2
6
AGND
XIC
Analog outputs
7
AO1
8
AO2
9
AGND
S600
AO1 I/U
X2
Aux. voltage output
10
+24V
11
DGND
12
DCOM
X3A
Programmable digital inputs DI1...DI3
13
DI1
14
DI2
15
DI3
X3B
Programmable digital inputs DI4...DI6
16
DI4
17
DI5
18
DI6
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
B+
30
A-
31
DGND
S4
TERM
S5
BIAS
X4
Safe torque off
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
Voltage/Current selection for analog input 1
Voltage/Current selection for analog input 2
Signal cable shield (screen)
External frequency reference 1: 0(2
Analog input circuit common
Reference voltage 10 V DC
Not used
Analog input circuit common
Output frequency: 0...20 mA
Output current: 0...20 mA
Analog output circuit common
Voltage/Current selection for analog output 1
Auxiliary voltage output +24 V DC
Auxiliary voltage output common
Digital input common for all
Start/Stop: Activate to start
Fwd/Rev: Activate to reverse rotation direction
Constant speed selection
Constant speed selection
Ramp pair selection: Activate to select 2nd pair
Not used
Ready run
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Faulted(-1)
250 V AC / 30 V DC
2 A
Embedded Modbus RTU (EIA-483)
Serial data link termination switch
Serial data link bias resistors switch
Safe torque off. Both circuits must be closed for
the drive to start.
)
...10 V