GENERAL DIAGRAM FOR TWO-STAGE L.P.G. PRESSURE REDUCTION FOR BURNER OR BOILER
E
N
G
L
I
S
H

AIR PRESSURE SWITCH

Regulate the air pressure switch after first carrying out all the other
burner adjustments with the air pressure switch adjusted to the start
of the scale. With the burner operating at a low flow rate (1st flame),
slowly turn the central screw clockwise until the burner locks out.
Then give the screw a half-turn anti-clockwise and repeat burner
start-up to check for proper operation. If the burner locks out again
give the screw another half-turn.

IONIZATION CURRENT

The minimum current needed to run the apparatus is 3µA.
The burner provides a significantly higher current and therefore
does not normally require any checks at all. In case, the ionisation
current need to be measured a microammeter must be connected
in series to the ionization electrode lead by opening the connector
"C" as illustrated in the figure.