Not TVEC II/VIK.qxd
PROBLEMS - ERROR MESSAGES
GB
Error messages (main errors)
E01
Overcurrent at constant speed
(fan at cruising speed)
E02
Overcurrent during deceleration
(fan about to stop)
E03
Overcurrent during acceleration
(fan is starting up)
E04
Overcurrent when stopped
E05
Motor overload
E09
Network undervoltage
E14
Earth leakage current
E15
Overvoltage on the power supply voltage
E08
EEPROM reading error
E11
E22
E21
Thermal protection of the device
After having resolved the cause of the error message, it is advisable to carry out a resetting of the errors (see P. 14).
In case of problems you can consult our After-Sales Department whilst indicating the identification N° located on one
of the sides of the micro-watt box (example: 5L8459).
11/04/06
15:38
Page 15
Description/cause
The regulator has detected an excessive output current (above the program-
med limit value):
- Terminals U, V, W under short circuit, motor cable under short-circuit,
- poor motor wiring or star/delta coupling,
- Motor is blocked or sharp increase in load,
Compatibility regulator/ motor (compatible motor power).
The motor has absorbed current that is too high for a certain time.
- A mechanical friction increases the motor load,
- Rated current of the motor is higher than the converter's protection current,
- Compatibility between the converter and motor
- An unconnected wire in the motor terminal block.
The mains network voltage is too low or unstable
- Check the tightening of nuts and bolts (filter, proximity disconnecting switch, converter)
- Short network power supply current interruptions
- Defective contactors
The regulator is protected against earth leakage currents whenever it is connected
to the mains network voltage and no operating order has been given.
- An input has been programmed with the "USP" function and the latter is active.
The power supply voltage is greater than the device's rated voltage
Processor operating error
Error in reading the parameters stored in the device's memory
- Temperature too high
The device has detected an over-temperature
- Lack of ventilation for the micro-watt box
- Internal cooling fan for the defective regulator