PROGRAMMATION OUVERTURE PIÉTON
The partial opening command can be activated through the PED input (term. 12) or with the second channel of the OC2
receiver (dip-switch 7 OFF);the options are those set for the Step-by-Step with function dip-switches 1 and 2.
In 2 motor mode (dip-switch 11 ON),the pedestrian command fully opens just the gate leaf with M1
In 1 motor mode (dip-switch 11 OFF),the pedestrian command partly opens the gate leaf with M1.The time is set at approx. 1/3
of total opening movement; to change the time, proceed as follows.
2
PROG.
P3
P/P
STOP
3
PED
4
PROGRAMMING THE PAUSE TIME
Procedure for modifying the pause time entered during previous programming.
This operation must be carried out with the gate closed.
1) Press the PROG button (part 17 fig. L) and hold it down until the LED LD1 (part 9 fig. L) remains constantly on.
2) Press the PROG button again; LED LD1 starts to blink and the control unit starts to memorise the pause time.
3) Press the PROG button again at the end of the pause time required. LED LD1 goes out and the procedure ends.
ADJUSTMENT OF SENSITIVITY
EN 12445 requires that every automation system must pass impact tests measured with a special instrument.
Carry out the impact tests and change the encoder sensitivity through the trimmer (part 8 fig. L).
If adjustments are insufficient to make values fall within the graph indicated by the above standard, we recommend installing a
soft rubber profile on the leading edge of the gate in order to soften impact.
If the requirements of the standard can still not be met after having adjusted the sensitivity and mounted the rubber profile,
alternative devices must be mounted, such as a safety edge on the leading edge of the gate.
Cut off the power supply to the control unit.
Release the motors and put the gate leaves in the "almost open" position.
Lock the motors and power the installation.
Press the PROG button (part 17, fig. E) and hold it down for about 3 seconds, until LED
LD1 (part 9, fig. E) remains constantly on.
LD1
The control unit is now in programming mode.
Press the PED button (connected to the input term. 12 or the memorized remote control).
The gate closes and when the limit position is acknowledged, it opens again automatically.
When the gate reaches the desired opening position, press the PED button again; the
control unit stores the time and closes the gate.
When the closing movement is complete, the control unit exits automatically from
programming.
PED
5
(pour automatisme à 1 moteur, dip 11 OFF)
6
t
GB
7
FINE PROG.