The connecting lines of the temperature sensors, may not be
shortened or extended.
A common routing in cable conduits or on cable racks with power
supply lines are not admissible.
The minimum distance for low voltage cables according to EN 1434 - 6 of
50 mm must be observed.

3.3.1 Installation in the ball valve with adapter

(5-piece coupling set in a separate bag)
Use ball valves with installation option for temperature sensor with thread
M10 x 1.
Installation (see fig. IV)
1. Close the ball valve.
2. Unscrew the plug screw from the ball valve.
3. Place the O-ring from the attached coupling set on the mounting pin.
4. Insert the O-ring with the mounting pin into the sensor hole of the ball
valve (turn the mounting pin).
5. Position the O-ring in its final position using the other end of the
mounting pin.
6. Fastening screw (plastic)
6.1 Put the fastening screw onto the temperature sensor.
7. Fastening screw (brass)
7.1 Slide the fastening screw onto the temperature sensor.
7.2 Slide the temperature sensor into the mounting pin up to the stop
and attach the fastening screw with the dowel pin.
7.3 Press in the dowel pin completely. Remove the mounting pin from
the temperature sensor.
8. Insert the temperature sensor with adapter fitting into the ball valve
and tighten fastening screw by hand (2-3 Nm).