3.3.2 Installation in a pocket
In case of new installations, MID heat meter or temperature sensors for
nominal sizes DN25 or smaller must only be installed directly immersed.
The objective of a symmetrical measure set-up with higher measuring
accuracy is thus supported.
3.4 Installing the integrator
Pay attention to sufficient distance between integrator and pos-
sible electromagnetic sources of interference (switches, electric
motors, fluorescent lamp, etc.) during installation.
At the flow sensor (see fig. VI-A)
Installation at medium temperature < 90°C and at T
With spacer (see fig. VI-B)
Installation at medium temperature > 90°C and at T
3.5 Functional testing
After installation of the meter, putting into operation and functional test-
ing can be performed.
Proceed as follows:
Open the stop valves
Check system for tightness
Bleed the system till the flow indication is stable. Adjust the system by
means of the flow indication
After a short while the message "E - 7" disappears in the display.
Press the push button next to the display and check the displays for
temperature and flow for plausibility.
Attach tampering protection at the integrator and the temperature
sensors.
Read and note meter data for energy, volume and serial number.