5  Technical Data

5 Technical Data

5.1 Specifications

Parameters
AC
Nominal apparent power
2)
Nominal active power
1)
Reactive power range
Nominal AC voltage (voltage range)
Supported grounding systems
Nominal AC current
Max. AC current
AC total harmonic distortion (THD at nominal output power)
Inrush current
Maximum residual output current
Power factor – standard
Displacement power factor
Stand-by power consumption (for communication)
Nominal power frequency (range)
DC
Input voltage range (at 400 Vac / at 480 Vac)
Nominal voltage DC (at 400 Vac / at 480 Vac)
MPP voltage range (at 400 Vac / at 480 Vac)
Initial input voltage (at 400 Vac / at 480 Vac)
Max. input voltage
Min. power on the grid
Max. input current / max. short-circuit current
Number of independent MPP inputs /
strings per MPP input
Overvoltage categories
Efficiency
Max. EU efficiency
EU efficiency at 630 VDC
CEC weighted efficiency (at 400 / at 480 Vac)
MPPT efficiency, static
Enclosure
38
STP60-10-IA-xx-11
1)
SMA Solar Technology AG / SMA Solar Technology America LLC
3P + PE (WYE) / 400 V to 480 V (± 10%)
3 x 87 A (3 x 72 A at 480 V)
Root-mean-square value 49.8 A over 3 periods
> 0.99 at nominal power
0 overexcited to 0 underexcited
50 Hz/60 Hz (± 10%)
565 V to 1000 V / 680 V to 1000 V
570 V to 800 V / 685 V to 800 V
1/1 (split up by external PV array junction box)
AC: Overvoltage category III (OVC III),
PV: Overvoltage category II (OVC II)
STP 60-10
60000 VA
60000 W
0 to 60000 var
TT, TN
3 x 87 A
< 1%
9.2 A/5 ms
3 W
630 V / 710 V
600 V / 720 V
1000 V
100 W
110 A / 150 A
98.8%
98.3%
98.0% / 98.5%
99.9%