AVENTICS | PROFIBUS DP | R402003657–BAL–001–AG
Commissioning and operation
and 0-byte inputs will be inserted, according to the GSD file.
4. Double-click the module BDC-B-DP_32.
A window is opened where the address of the bus coupler
can be entered. In the E/A Einstellungen (I/O settings) area,
you can set the start address of the output of the module.
In the Herstellerspezifische Daten (Manufacturer-specific
data) area, you can change the user parameters (5 bytes).
In byte 0, the value may be changed from 00 Hex to 04 Hex. 00
Hex means that the internal watchdog works with a time basis
of 10 ms. At 04 Hex it works with 1 ms. AVENTICS recommends
the 00 Hex setting.
Bytes 1, 2, 3, 4 must have value 00.