Carel μChiller Manual Del Usuario página 89

Tabla de contenido

Publicidad

Index
Size
Ref.
162
1
C012
163
1
C013
164
1
C014
165
1
C015
166
1
C016
167
1
S021
168
1
C020
169
1
C021
170
2
C022
172
2
C023
174
2
C024
176
2
C025
178
2
C026
180
2
C027
182
2
C028
184
2
C029
186
2
C030
188
2
C031
190
2
C032
192
2
C033
194
1
C037
195
2
C038
197
2
C039
199
1
C040
200
2
C041
202
2
C042
204
1
C043
206
1
C046
207
1
C047
208
1
C048
209
1
S000
210
1
S002
212
1
S022
214
1
S008
215
1
S010
216
1
S011
217
1
S012
218
1
S014
219
1
S015
220
2
S016
222
2
S017
224
2
S018
226
1
S019
227
2
229
2
Sprb
231
2
S025
233
1
S026
234
1
S027
235
2
S028
237
2
S029
241
2
S031
243
1
S032
246
2
S034
248
2
S035
250
2
S036
252
2
S037
254
2
S039
256
2
S040
258
1
S041
259
2
S042
261
1
S044
262
1
S045
263
1
S046
264
1
S047
265
1
S048
266
1
S049
267
1
S050
272
1
S053
274
2
S054
278
1
S056
279
2
S057
281
2
S058
283
1
S059
284
2
S060
μchiller +0300053ES rel. 2.0 - 07.07.2020
Type
Min/Max
R/W
UoM
INT
30..999
R/W
s
INT
30..999
R/W
s
INT
300..999
R/W
s
INT
10..999
R/W
s
INT
5..999
R/W
s
INT
0..23
R/W
h
INT
5..999
R/W
min
INT
0..1
R/W
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
bar/psi C026 - Discharge press. probe offset for circ.1
REAL
-99.9..99.9
R/W
bar/psi C027 - Suction press. probe offset for circ.1
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
bar/psi C030 - Discharge press. probe offset for circ.2
REAL
-99.9..99.9
R/W
bar/psi C031 - Suction press. probe offset for circ.2
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
K/R
INT
0..1
R/W
REAL
-1.0..99.9
R/W
bar/psi C038 - Suction press. probe min value
REAL
0.0..99.9
R/W
bar/psi C039 - Suction press. probe max value
INT
0..1
R/W
REAL
-1.0..99.9
R/W
bar/psi C041 - Discharge press. probe min value
REAL
0.0..99.9
R/W
bar/psi C042 - Discharge press. probe max value
INT
0..1
R/W
INT
1..2
R/W
INT
0..1/3
R/W
INT
1..2
R/W
INT
0..999
R/W
h
INT
0..2
R/W
INT
0..59
R/W
min
INT
0..999
R/W
h
INT
0..2
R/W
INT
0..101
R/W
%
INT
0..999
R/W
h
INT
0..2
R/W
INT
0..101
R/W
%
REAL
-999.9..999.9
R/W
°C/°F
REAL
0..100
R/W
%
REAL
0..100
R/W
%
INT
0..300
R/W
s
REAL
R/W
%
REAL
R
°C/°F
REAL
0..999.9
R/W
°C/°F
INT
0..999
R/W
s
INT
0..999
R/W
s
REAL
-999.9..999.9
R/W
°C/°F
REAL
0..99.9
R/W
°C/°F
REAL
0..999.9
R/W
°C/°F
INT
0..999
R/W
s
REAL
0..99.9
R/W
K/R
REAL
0..99.9
R/W
K/R
REAL
0..100
R/W
%
REAL
0..100
R/W
%
REAL
-99.9..99.9
R/W
°C/°F
REAL
S039..99.9
R/W
°C/°F
INT
0..999
R/W
min
REAL
-999.9..999.9
R/W
°C/°F
INT
0..999
R/W
s
INT
0..999
R/W
s
INT
0..99
R/W
min
INT
0..99
R/W
min
INT
0..999
R/W
s
INT
0..999
R/W
s
INT
0..999
R/W
min
INT
0..2
R/W
REAL
0..999.9
R/W
bar/psi S054 - Delta press. to reverse the 4 way valve
INT
20..999
R/W
s
REAL
-999.9..999.9
R/W
°C/°F
REAL
0..999
R/W
K/R
INT
0..999
R/W
s
REAL
-99.9..99.9
R/W
K/R
Description
C012 - Compr. min On time
C013 - Compr. min Off time
C014 - Min time between On of same compr.
C015 - Compr. load up time
C016 - Compr. load down time
Time band hour
C020 - Circuit destabilization max time with one or more compr. OFF
C021 - Circuit power distribution (0=Equalized, 1=Grouped)
C022 - Discharge temp. probe offset for circ.1
C023 - Suction temp. probe offset for circ.1
C024 - Discharge temp. probe offset for circ.2
C025 - Suction temp. probe offset for circ.2
C028 - Cond. temp. probe offset for circ.1
C029 - Evap. temp. probe offset for circ.1
C032 - Cond. temp. probe offset for circ.2
C033 - Evap. temp. probe offset for circ.2
C037 - Suction press. probe type (0=0..5V, 1=4..20mA)
C040 - Discharge press. probe type (0=0..5V, 1=4..20mA)
C043 - Discharge temp. probe type (0=NTC, 1=NTC-HT)
C046 - Number of circuit in the unit
C047 - Type of compressors used
(0=1 ON/OFF, 1=2 ON/OFF, 2=BLDC, 3=BLDC + ON/OFF)
C048 - Compressor rotation type (1=FIFO, 2=TIME)
S000 - Source pump 1 maintenance hour threshold (x100)
S002 - Source pump 1 manual mode (0=AUTO, 1=OFF, 2=ON)
Time band minute
S008 - Source fan 1 circ.1 maintenance hour threshold (x100)
S010 - Source fan ON/OFFcirc.1 manual mode (0=AUTO, 1=OFF, 2=ON)
S011 - Source fan inverter circ.1 manual mode(0=AUTO, 1=0%, 2=1%, .. 101=100%)
S012 - Source fan 1 circ.2 maintenance hour threshold (x100)
S014 - Source fan ON/OFF circ.2 manual mode (0=AUTO, 1=OFF, 2=ON)
S015 - Source fan inverter circ.2 manual mode (0=AUTO, 1=0%, 2=1%, .. 101=100%)
S016 - Source fan temp. threshold for cold climates
S017 - Source fan min speed for cold climates
S018 - Source fan speed up speed for cold climates
S019 - Source fan speed up time for cold climates
FC_PrwReq - Free-Cooling regulation ramp
SPrb - Source external air temperature
S025 - Low noise source fan setpoint in cooling
S026 - Compr. delay ON since the source pump ON
S027 - Source pump delay OFF since the compr. OFF
S028 - Source fan cool setpoint
S029 - Source fan heat setpoint
S031 - Source fan cool setpoint at startup
S032 - Source fan cool startup delay
S034 - Source fan cool differential
S035 - Source fan heat differential
S036 - Source fan inverter min speed
S037 - Source fan inverter max speed
S039 - Defrost start threshold
S040 - Defrost start threshold reset
S041 - Defrost start delay
S042 - Defrost end threshold
S044 - Defrost begin delay before actuating the 4 way valve
S045 - Defrost ending delay after actuating the 4 way valve
S046 - Defrost min duration
S047 - Defrost max duration
S048 - Dripping duration
S049 - Post dripping duration
S050 - Delay between defrosts
S053 - Defrost synchronization type
(0=Independent, 1=Separated, 2=Simultaneous)
S056 - Duration of smart start function
S057 - Antifreeze source alarm threshold
S058 - Antifreeze source alarm differential
S059 - Antifreeze source alarm delay time at 1K below threshold
S060 - Source external air temperature offset
SPA
89

Publicidad

Tabla de contenido
loading

Tabla de contenido