baltur TBML 600 ME Manual De Instrucciones página 14

Quemadores mixtos de gas / gasóleo a modulación electrónica con equipo bt 340
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 31
DIAGRAM ILLUSTRATING GAS TRAIN PRINCIPLE
Install a manual on/off valve upstream of the gas valve and
a vibration-proof joint according to the layout shown in the
diagram illustrating the principle.
To ensure optimal functioning of the pressure control, it should
be applied to the horizontal pipe after the filter. The gas pressure
regulator must be adjusted while operating at the maximum flow
rate actually used by the burner. The outgoing pressure must
be adjusted to a value slightly below the maximum possible
value (the value obtained by screwing in the adjustment screw
almost completely); in this case, the outgoing regulator pressure
increases as the adjustment screw is tightened, and decreases as
it is slackened.
DIAGRAM ILLUSTRATING DUAL FUEL BURNERS SERIES TBML 600 / 800
TO BE SUPPLIED BY INSTALLER
LIMITS ON BALTUR SUPPLY
DIESEL RETURN
DISELE INTAKE
1
Air regulation servomotor
2
Air pressure switch
3
Maximum gas pressure switch
4
Gas supply modulating control butterfly valve
5
Operating gas valve with pressure regulator
6
Valve seal control device (integrated in the equipment)
7
Safety gas valve
8
Minimum pressure switch and gas leak control.
9
Gas filter
10
Vibration-proof joint (not included in supply)
11
Ball cock (not included in supply)
12
Gas / diesel regulator servomotor
13
Diesel return flow rate regulator
14
Diesel solenoid valve (NC)
15
Pressure gauge 0÷40 bar
16
Burner pump (25 bar)
17
Pump motor
18
Hose
19
Diesel filter
20
Maximum diesel pressure switch
12 / 28
0006081557_201310

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tbml 800 me

Tabla de contenido