Select group 02 ORIENTED START-UP
- Change the content of P0317 for "[001] Yes".
3
- Press "Save".
- Select the desired language.
4
- Press "Save".
IMPORTANT: the PM with encoder control mode must be selected
only when the motor is equipped with encoder (speed sensor).
5
- Select the control mode: [006] PM with encoder or [007]
Sensorless PM.
- Press "Save".
- Set P0296 according to the line rated voltage.
6
- Press "Save".
Set P0298 according to the application:
ND: normal duty overloads for long periods.
7
HD: heavy overloads for short periods.
For further information, refer to the inverter overload curves in Chapter
8 Technical Specifications of the User's Manual.
The next parameters must be set according to the motor nameplate.
- Change the content of P0398 according to the motor service factor.
8
- Press "Save".
- Change the content of P0400 according to the motor rated voltage.
9
- Press "Save".
- Change the content of P0401 according to the motor rated current.
10
- Press "Save".
- Change the content of P0402 according to the motor rated speed.
11
- Press "Save".
At this moment, the oriented start-up routine starts
and the "config" status is indicated on the upper part of the HMI
Quick Guide
PM Sensorless
PM Sensorless
400 V
400 V
Normal Duty
1.00
1.00
400 V
400 V
26.1 A
26.1 A
1500 rpm