Remote controller
MELANS display
display
UE
1302
UL
1300
F8
4115
P1
5101
P2
5102
P4
2503
P5
2502
P5
2500
P6
1503
P6
1504
P8
1110
P9
5103
•
Depending on the position of the SW2 switch on the outdoor unit board, the segments light up to indicate the running condition of the unit and the particulars of the check
code.
SW2 setting
123456
Operation mode/relay output
000000
011110
Outdoor unit control condition
Indoor-side control condition
010110
011100
Error code history 1
Error code history 2
111100
*1 Display system for error indicator
The indicator corresponds to the following numbers
0 ............. Outdoor unit
1 ............. Indoor unit
13.2. The following occurrences are not problems or errors
Problem
The fan setting changes during heating.
The fan stops during heating.
When the switch is turned ON, the fan does
not begin to operate.
The outdoor-side fan turns in reverse or stops,
and an unusual sound is heard.
Note:
If indoor-side fan does not operate, check the over-current relay on the fan motor to determine whether it has been tripped.
If the over-current relay has been tripped, reset it after eliminating the cause of the problem (e.g. motor lock).
To reset the over-current relay, open the control box and press the green claw on bottom-right of the relay until a click is heard. Release the claw and check that
it returns to its original position.
Note that if it is pressed too hard it will not return to its original position.
18
High pressure error (63H1 operation)
Low pressure error (63L operation)
Power synchronous idle circuit error
Inlet sensor error
Piping (liquid pipe) sensor error
Drain sensor error
Drain overflow protector operation
Water leak error
Freeze prevention operation
Surge prevention operation
Piping temperature error
Piping (2-phase pipe) sensor error
Item
tens place
units place
When an error occurs, the error code
and error signal (*1) are displayed in
alternation.
Control mode display system
(IC1)
Nothing
The error code (ex. U8, UA) and error indicator (*1) are displayed in alternation.
Remote controller display
Ordinary display
Defrosting display
Heating preparations
underway
Ordinary display
Error details
Display contents
O: stop
C: cooling
H: heating
d: defrosting
1: SV1
Relay output = SV1 + 21S4 + 52C
2: 21S4
4: 52C
Ex. During cooling mode, when 52C and SV1 are ON: C5
Display
0
1
2
Indoor-side
3
Outdoor-side
4
5
6
7
During thermostat OFF mode, light air or low air operation will take place.
During thermostat ON mode, light air or low air will switch automatically to set notch on
the basis of time or piping temperature.
During defrosting, the fan will stop.
After the switch is turned to ON or until the piping temperature reaches 35°C, there will
be 5 minutes of light air operation. After that there will be 2 minutes of low air operation,
then set notch will begin (hot adjustment control).
There is a risk of the power to the unit being connected in reverse phase. Be sure to
check that the phase is correct.
Problem location
Outdoor-side controller board
Outdoor-side controller board
Outdoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Indoor-side controller board
Control mode
Indoor-side
Outdoor-side
←
Ordinary
←
Hot adjustment
←
Defrosting
←
—
←
Heater ON
←
Freeze prevention
←
Surge prevention
←
Compressor OFF
Cause