Access Level Description; Output Values - Carrier 80HMA Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 137
Variable table
Nr.
Name
Par.
User Interface address
User Interface
associated to the relevant Board
126
Connected
(at Par. 127) and Zone (Par. 22)
Address
0. No User Interface connected
Address of the board which
127 Board address
Variable Table is shown
User Interface
Shows the address of the User
128
self Address
Interface being used

Access Level description

Each board has a different Access Level (Par. 125); the user
interface inherits the access level from the virtual zone to
whom is associated.
Master Board always has access level 3, while for slave
boards access level is customizable.
The access level defines the operation that user can do
through the user interface.
Access Level 0: The user can only manage the own zone,
modify the setpoint and modify the mode between OFF
and the mode of Master, but he can't modify the schedule
and change the installation settings. It can be used for Slave
board installed in hotel rooms or when the user has to have
the lowest possibility to change the working parameters.

Output values

NOTE: if the output has positive configuration, output is
HIGH when the corresponding device has to be activated.
If the output has negative configuration, output is LOW
when corresponding device has to be activated.
Nr.
0
1
2
3
4
5
6
7
24 80HMA
Description
Master
Name
Description
Not used
Output not configured. Output always LOW
Water pump
Controls the additional water pump
Sanitary water valve
Sanitary hot water valve control
Electric heater A
Control of the 3 heating steps (backup heaters).
Electric heater B
Electric heater C
Control of the 3 heating steps (backup heaters).
Electric heater X
Electric heater Y
Available on
User
Slave Pool
Interface
x
x
x
x
x
Access Level 1: The user has the same limitation of Access
Level 0, but he can change the schedule. It can used for
installation where every zone of Slave board is used to
manage the comfort of a house or where the user can be
independent from the working operation of the other zone
of the same Slave board.
Access Level 2: The user can operate as per Access Level
1, but in addition, using the Zone key, he can connect to
-
virtual zone
(other zone of the same slave board).
Access Level 3: The user can change the target address and
zone (Virtual zoning features are fully active). He can change
the master mode by connecting to virtual zone
as the local mode by operating on local zones.
Parameters in the variable table are grouped by access level.
All the descriptions are referred to positive configurations.
Example:
1
if the water pump is requested ON, the output is high
-1
if the water pump is requested ON, the output is low
First step: turn on only A
Second step: turn on only A and B
Third step: turn on A, B and C
First step: turn on only X
Second step: turn on only Y
Third step: turn on X and Y
RANGE
Heat
MIN
MAX DEFAULT
Pump
85
213
0
Own
0
255
address
Own
85
213
address
, as well

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido