WIRING DIAGRAMS
INSTALLATION
Control configuration
Spring clamps -AB+ and CP connection
The spring terminals intended for the electrical connections are compatible with 0 .2 to 1 .5 mm² section rigid or flexible
cables, while if they are provided with
lugs with plastic collar, their maximum
section is reduced to 0 .75 mm² .
For correct and secure connection
follow the operations below:
- strip the cable by 8 mm as shown
below;
- if the cable is rigid you should be
able to insert its end easily, while if it is
flexible you should use a pair of nose
grippers;
- insert the cables completely and make
sure they are properly fixed by pulling
them slightly;
2
8mm
0.2-1.5mm
- to disconnect the cables use a
screwdriver to press the corresponding
white notch (ref .C) and remove the
A
conductor .
C
Remote terminal TC-R PLUS connection
Group configuration for control CC-R PLUS
Connect the RS485 line of the wall-mounted remote control to one or more (up to a maximum of 30) units equipped
with electronic remote control CC-R Plus through a bipolar cable suitable for RS485 serial connection, keeping it
separate from power supply cables .
- Chase out the wall in order to minimise the length of the leads;
- complete the line with the 120 Ω resistance supplied;
- do not make "star" connections;
- the connection with cable RS485 is polarised, observe the indications "A" and "B" on each peripheral device
connected (for the connection it is preferable to use a bipolar shielded cable with a minimum section of 0 .35 mm
);
2
connect the + and - power supply terminals of the wall-mounted terminal, 5 V DC voltage, on one of the TC-R Plus
boards, respecting the polarities .
Fig .1
24