Descargar Imprimir esta página

Installation Instructions; Electrical Requirements - Friedrich Hazardgard Article 501 Manual De Instalación Y Funcionamiento

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation Instructions

Models SH15, SH20 and SH24
NOTE: THIS MANUAL INCLUDES INSTALLATION INSTRUCTIONS FOR BOTH WINDOW MOUNT
AND THROUGH- THE WALL INSTALLATIONS
WARNING
Explosion Hazard
Electrically connect unit in accordance with NEC
Code Article 501. Failure to do so can result in
death, explosion, fire or electrical shock

Electrical Requirements

ALL FIELD WIRING MUST MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE (ANSI/NFPA
70) ARTICLE 501.
THE FIELD-PROVIDED CIRCUIT PROTECTION DEVICE (HACR CIRCUIT BREAKER OR TIME DELAY FUSE) MUST NOT EXCEED THE
AMPACITY INDICATED ON THE PRODUCT NAMEPLATE.
IMPORTANT: Before you begin the actual installation of your air conditioner, check local electrical codes and the information below.
Your power supply must be the same A.C. voltage and frequency (hertz) as marked on the name plate located on the chassis. Only
alternating current (A.C.), no direct current (D.C.), can be used.
An overloaded circuit will invariably cause malfunction or failure of the air conditioner; therefore, it is extremely important that the
electrical power is adequate. Consult your dealer or power company if in doubt.
The following instructions are for HAZARDGARD models and cabinet sizes listed below.
GROUPS
SMALL CHASSIS SH15
MEDIUM CHASSIS SH20, SH 24
Model Number
SH15
SH20, SH24
Electrical Shock Hazard
CABINET SIZE (H x W X D)
15 15/16" x 25 15/16" x 27 3/8"
(405 mm x 660 mm x 695 mm)
17 15/16" x 25 15/16" x 27 3/8"
(455 mm x 660 mm x 695 mm)
Plug Type
Circuit Rating
Time Delay Fuse
Junction Box
250V-15 Amp
Junction Box
250V-15 Amp, 250V-20 Amp
7

Publicidad

loading

Este manual también es adecuado para:

Hazardgard article 505