Diagram to signals
4. opERaTion
step 1: After installing the module, energize the inverter;
step 2: Check if the module has been correctly identified by the control:
P0027=xxC2;
step 3: Program parameter P0202 (Type of control) = 4 (Vectorial with encoder).
This way, the inverter will operate with speed feedback for the encoder in-
cremental. The number of pulses per encoder rotation must be programmed
in P0405.
noTE!
See the CFW11 Manual for more details on the Vectorial Control.
Signal
A
A
B
B
Figure 8: Standard phase of the encoder signals
Time