Controlling the ED12
Malfunction caused by closed housing ventilation port!
If the housing ventilation port is closed, there is no atmospheric equalization and the
characteristics curve will change.
Ensure that the air can circulate freely through the housing ventilation port (2).
Never operate the device in an atmosphere containing oil.

8.2.1 Characteristic curves

The characteristic curves for all ED12 models are depicted below,
sorted according to outlet pressures.
NOTICE

8.2.2 Outlet pressure 0 to 10 bar

[bar]
10
7,5
5
2,5
0
0
5
10
15
0%
Set point/
actual value
R414001635
R414000728
R414001637
[ba r]
10
7,5
5
2,5
0
0
2,5 5
0%
Set point
R414000730
R414001639
Use the characteristic curves from the respective offer
drawings for devices with other pressure ranges.
[bar]
145 [psi]
72,5
0
20
[mA]
100%
00121347
R414001636
R414000729
R414001638
[bar]
145 [ps ]
72, 5
0
7,5 10
[V]
100%
00121349
R414000731
R414001640
10
145 [psi]
7,5
5
2,5
0
4
8
12
16
20
0%
100%
Set point/
00121348
actual value
10
145 [psi]
7,5
5
2,5
0
0
2,5
5
7,5
10
0%
100%
Set point/
00125300
actual value
72,5
0
[mA]
72,5
0
[V]