RS485-B Communication Plug-in Module
NOTE!
For the CFW500-CRS485-B-PNP module,
the digital inputs are fixed at active high
(P0271 = 8). It is not possible to set P0271
different from 8.
The location of the DIP-switches for selecting the type
of analog input and output signal and termination of
the RS485 line can be better visualized in
To use the analog inputs and/ or outputs with signal in
current, switch S1 and related parameters must be set as
indicated in
table 2
connections see chapter 3 - Installation and Connection
of the CFW500 user's manual.
Table 2: Settings of switches to select the type of analog
input and output signal of the CRS485-B
Input /
Signal
Output
Voltage
AI1
Current
Voltage
AI2
Current
Voltage
AO1
Current
NOTE!
Any other combinations of the switches
are not allowed
. For further details about the control
Setting of
Switch S1
S1.1 = OFF
S1.1 = ON
S2.1 = OFF
S2.1 = ON
S1.2 = ON
S1.2 = OFF
Configurations for activation of RS485 (1):
S1.3 = ON and S1.4 = ON: RS485
termination ON
S1.3 = OFF and S1.4 = OFF: RS485
termination OFF
Range of
Parameter
Signal
Settings
0...10 V
P0233 = 0 or 2
0...20 mA P0233 = 0 or 2
4...20 mA P0233 = 1 or 3
0...10 V
P0238 = 0 or 2
0...20 mA P0238 = 0 or 2
4...20 m A P0238 = 1 or 3
0...10 V
P0253 = 0 or 3
0...20 mA P0253 = 1 or 4
4...20 mA P0253 = 2 or 5
figure
A.2.