Setting the number of parameter data words (PCP)
ƒ You can use switches 5 and 6 or the code C13892 / C14892 to set the number of
parameter data words.
ƒ 0, 1, 2 or 4 parameter data words can be used.
ƒ The current setting is shown in C13860/1 / C14860/1.
)
Note!
The total number of data words (PD + PCP) must be between 1 and 10.
Impermissible settings are signalled by the "BE" LED (flashes
The communication module then works internally with the following values:
PD = 2 (words)
ƒ
PCP = 1 (word)
ƒ
DIP switch
ON
OFF
EDK94AYCIB DE/EN/FR/ES/IT 2.0
Number of PCP
0
OFF
1
OFF
2
ON
4
ON
l
Possible settings via DIP switch
Max. number of
Switch
5
6
OFF
ON
OFF
ON
Commissioning
^ 55
) red).
ID code
PD
[hex]
10
0x03
9
0xE3
8
0xE0
6
0xE1
7