Fault / Alarm
F0769
Fault that indicates the broken belt
Broken Belt
condition was detected for the motor
Detected
driven by the CFW501 frequency
inverter.
F0771
Fault that indicates the need of
Filter maintenance
replacing the system filter.
F0773
"Installed plug-in module does not
HVAC Plug-in
correspond to the plug-in module
Module not
specific for the HVAC function
Detected
(CFW500-CRS485)."
F0787
Fault that indicates the feedback of the
Low Level of the
external PID controller has a low value.
Process Variable
of the External PID
Controller
F0789
Fault that indicates the feedback of the
High Level of the
external PID controller has a high value.
Process Variable
of the External PID
Controller
P0047
0
Out of CONFIG status, HMI, P0006 and P0680 must not indicate CONF.
5
Two or more DIx (P0263...P0270) programmed for direction of rotation (4).
6
Two or more DIx (P0263...P0270) programmed for LOC/REM selection (5).
9
Two or more DIx (P0263...P0270) programmed for 2
11
Two or more DIx (P0263...P0270) programmed for disable Flying-Start (15).
12
Two or more DIx (P0263...P0270) programmed for lock programming (17).
13
Two or more DIx (P0263...P0270) programmed for load user 1 (18).
14
Two or more DIx (P0263...P0270) programmed for load user 2 (19).
Run-Stop command (P0224 or P0227) programmed for Dix (1) without DIx (P0263...P0270) programmed
for (1 = Run/Stop) and without DIx (P0263...P0270) programmed for general enable (2) and without
19
DIx (P0263...P0270) programmed for quick stop (3) and without DIx (P0263...P0270) programmed for
advance(4) and without DIx (P0263...P0270) programmed for start (6).
20
Digital input DI2 (P0265) programmed for PTC (29) or analog input AI3 (P0241) programmed for PTC (4).
Reference (P0221 or P0222) programmed for AI2 (2) or AI3 (3) and the plug-In module has no AI2 and
25
AI3.
26
P0312 programmed for REMOTE HMI (0 or 6) without HMI connected.
27
Poor configuration of the V/f curve (P0142 to P0147) causes voltage step in the output).
Bypass mode configured (P0583) without any digital input configured for "Activate bypass";
Bypass mode configured with more than one digital input configured for "Activate bypass";
28
Bypass mode configured without a digital output configured for "Contactor bypass drive" and a digital
output configure to "Mains bypass contactor";
Bypass mode configured and either of the two bypass digital outputs with duplicated configuration.
"Fire Mode" configured without a digital input configured for "Activate Fire Mode";
More than one digital input configured for "Activate Fire Mode";
29
More than one digital output configured for "Fire Mode active";
Digital input configured for "Fire Mode" with the "Fire Mode" function disabled;
Digital output configured for "Fire Mode" with the "Fire Mode" function disabled.
Quick Parameter Reference, Faults and Alarms
Description
Origin Situation of CONFIG Status
Possible Causes
Parameter P1046 is programmed for 2 and the motor
driven by the CFW501 frequency inverter is running
with speed above the speed programmed in P1047
and the motor torque remained below the value
programmed in P1048 for the time programmed
in P1049.
Parameter P1050 is programmed for 2 and the
operation time of the motor driven by the CFW501
frequency inverter shown in P1052 is above the value
programmed in P1051.
HVAC application active (P1003 = 1) without the
standard plug-in CFW500-CRS485.
Parameter P1075 is programmed for 2 and the value
of the process variation of the external PID controller
remained below the value programmed in P1076 for
the time programmed in P1077.
Parameter P1075 is programmed for 2 and the value
of the process variation of the external PID controller
remained above the value programmed in P1078 for
the time programmed in P1079.
nd
ramp (8).
CFW501 | 25