Param.
Function
P0258 FO Gain
P0259 Min. FO
P0260 Max. FO
P0263 DI1 Function
P0264 DI2 Function
P0265 DI3 Function
P0266 DI4 Function
P0267 DI5 Function
P0268 DI6 Function
P0269 DI7 Function
P0270 DI8 Function
P0271 DI1 Function
Quick Parameter Reference, Faults and Alarms
Adjustable Range
0.000 to 9.999
10 to 20000 Hz
10 to 20000 Hz
0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Quick Stop
4 = FWD/REV
5 = LOC/REM
6 = JOG
7 = SoftPLC
8 = 2
Ramp
nd
9 = Not Used
10 = Not Used
11 = Not Used
12 = No Ext. Alarm
13 = No Ext. Fault
14 = Reset
15 = Disab.FlyStart
16 = Not Used
17 = Progr. Off
18 = Load User 1
19 = Load User 2
20 = Auto/Manual Main PID
21 = Auto/Manual External
PID
22 = Not Used
23 = Bypass Mode
24 = Activate Fire Mode
25 = PTC
See options in P0263
See options in P0263
See options in P0263
See options in P0263
See options in P0263
See options in P0263
See options in P0263
0 = (DI1..DI8)NPN
1 = DI1 PNP
2 = (DI1..DI2)PNP
3 = (DI1..DI3)PNP
4 = (DI1..DI4)PNP
5 = (DI1..DI5)PNP
6 = (DI1..DI6)PNP
7 = (DI1..DI7)PNP
8 = (DI1..DI8)PNP
Factory
User
Propr. Groups Pag.
Setting
Setting
1.000
10 Hz
10000 Hz
1
cfg
0
cfg
20
cfg
21
cfg
0
cfg
0
cfg
0
cfg
0
cfg
0
cfg
I/O
12-15
I/O
12-15
I/O
12-15
I/O
12-17
I/O
12-17
I/O
12-17
I/O
12-17
I/O
12-17
I/O
12-17
I/O
12-17
I/O
12-17
I/O
12-15
CFW501 | 11