W
A
R
!
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in a manner intended by the manufacturer. If you
have questions, contact the manufacturer.
2. Before servicing or cleaning the unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. when the service
disconnecting means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
4. Sufficient air is needed for proper combustion and exhausting of
gasses through the flue (chimney) of fuel burning equipment to
prevent backdrafting. Follow the heating equipment manufacturer's
guideline and safety standards, such as those published by the
National Fire Prevention Association (NFPA), and the American
Society for Heating, Refrigeration and Air-Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall(s) or ceiling, do not
damage electrical wiring or other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. If this unit is to be installed over a tub or shower, it must be marked
as appropriate for the application and be connected to a GFCI
(Ground Fault Circuit Interrupter) - protected branch circuit.
8. Never place a switch where it can be reached from a tub or shower.
9. Install fan at least 5 feet (1.52 m) above the floor.
10. This unit must be grounded.
11. Unit must not be installed in a ceiling thermally insulated to a value
greater than R40.
C A U T I O N
!
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy/unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
3. DO NOT install this product in a wall. This product is designed
for installation in ceilings up to a 12/12 pitch (45 degrees).
Ductwork must point upward.
4. Please read specification label on product for further
information and requirements.
PREVENTATIVE MAINTENANCE
A clean fan provides better service. Disconnect the power supply and
clean the fan as listed below.
TO CLEAN GRILL
dishwashing liquid, and a soft cloth. DO NOT use abrasive cloths,
steel wool pads or scouring powders.
TO CLEAN FAN ASSEMBLY: Unplug motor cord from receptacle. To
remove motor plate, find the single tab on the motor plate (located
next to the receptacle). Push up rear motor plate tab while pushing out
on the side of the housing or insert a screwdriver into the slot in the
housing (next to tab) and twist screwdriver. Gently vacuum fan, motor
and interior of housing.
METAL AND ELECTRICAL PARTS SHOULD NEVER BE IMMERSED
IN WATER.
N
I
N
G
: Use a mild detergent, such as
43053-01 12/01/2013
MAINTENANCE
The motor is permanently lubricated and never needs oiling. If the
motor bearings are making excessive or unusual
noises, replace the motor with the exact service motor. You should
replace the impeller at the same time.
W A R N I N G
!
DISCONNECT ELECTRIC
POWER SUPPLY
AND LOCK OUT
SERVICE PANEL BEFORE
SERVICING UNIT
COOKING AREA
Do Not Install Above
Or Inside This Area
45°
Equipment
BATHROOM AREA
3ft. min.
Tub /
Shower
2
45°
Floor
Cooking
Bath Fan
8ft. min.