Fault/Alarm
A0139:
It indicates an interruption in the
(2)
Offline Profibus DP
communication between the Profibus DP
Interface
network master and the inverter.
A0140:
It indicates an error in the access to the
(2)
Profibus DP
Profibus DP communication module
Module Access
data.
Error
F0150:
Overspeed fault.
Motor Overspeed
It trips when the actual speed exceeds
the value of P0134 x
more than 20 ms.
F0151:
FLASH Memory Module (MMF-01) fault.
FLASH Memory
Module Fault
A0152:
This alarm indicates that the internal air
High Internal Air
temperature is too high.
Temperature
Note:
It can be disabled by setting
P0353 = 1 or 3.
F0153:
It indicates internal air overtemperature
Internal Air
fault.
Overtemperature
F0156:
The temperature sensors located in the
Undertemperature
IGBTs or in the rectifier detected a low
temperature, below
-30 °C ( -22 °F), fault.
F0157:
There was a problem during the
Parameter Table
initialization, during the parameter table
Data Loss
loading routine. Some recent parameter
modifications may have been lost.
F0158:
There was a problem during the
Parameter Table
initialization, during the parameter table
Fault
loading routine. All the parameters were
lost and the factory settings were loaded.
A0159:
Incompatible HMI
Incompatible HMI
F0160:
STO function (Safe Torque Off) relay fault.
Safety Stop Relays
A0163:
It indicates that the AI1 current
AI1 Broken Cable
(4-20 mA or 20-4 mA) reference is out of
the 4 to 20 mA range.
A0164:
It indicates that the AI2 current (4-20 mA or
AI2 Broken Cable
20-4 mA) reference is out of the 4 to 20
mA range.
A0168:
Difference between Speed Reference and
Speed Error too
Effective Speed greater than the setting
High
in P0360.
F0169:
Difference between Speed Reference and
Speed Error too
Effective Speed greater than the setting in
High
P0360 for longer than P0361.
A0170:
The STO function (Safe Torque Off) is
Safety Stop
active.
Quick Parameter Reference, Faults and Alarms
Description
(100 % + P0132)
for
100%
Possible Causes
Verify whether the network master is correctly
configured and operating normally.
Verify the network installation in a general manner
- cable routing, grounding.
Refer to the Profibus DP communication manual
for more information
.
(3)
Verify whether the Profibus DP module is correctly
fit into the slot 3.
Refer to the Profibus DP communication manual
for more information
.
(3)
Wrong settings of P0161 and/or P0162.
Problem with a hoist-type load.
Defective FLASH memory module.
Check the connection of the FLASH memory
module.
High surrounding air temperature (>50 °C (122 °F))
and high output current.
Defective internal fan (if existent).
High temperature (> 45 ºC) inside the cabinet.
High surrounding air temperature (>50 °C (122 °F))
and high output current.
Defective internal fan (if existent).
Surrounding air temperature ≤ -30 °C (-22 °F).
The control was switched off very fast while a
parameter was being modified.
Firmware updating fault.
Defective control board.
HMI of another product being used.
One of the relays is defective or it does not have +24
V applied to its coil.
Broken AI1 cable.
Bad contact at the connection of the signal to the
terminal strip.
Broken AI2 cable.
Bad contact at the connection of the signal to the
terminal strip.
Inverter in Torque Current Limitation.
Inverter in Torque Current Limitation for too long.
The CFW700 went to the STO state.
CFW700 | 25