Then, the detector Leds will start to blink if the detectors are correctly installed. Go over
the entire installation to check that this occurs in all the detectors as indicated.
To exit this mode:
1. Press TEST MODULE/LINE
Don't forget to reconnect the module line by pressing ON/OFF
In equipments Portuguese standard

5. FAULT INDICATORS AND MESSAGES DISPLAYED

Line error
Line fuse error
Line voltage error
When the causes that produced these statuses disappear, the indicators will be restored
again automatically.
and the display will show:
will be
Detectors incorrectly connected.
Detectors not installed.
Line cut off.
Check cause.
The line fuse has blown.
There is a short-circuit or too many detectors have
been connected to the line.
Check cause.
Disconnect the module line and replace the fuse with
an identical one.
The line voltage is not correct.
There is an unsuitable section of cable.
Too many detectors are connected to the line.
Excessive line length.
Detector incorrectly assembled to its base.
Disconnect the module line and check the cause.
47