Elevation Stops
The.Aeromaster.12™.has.120°.of.travel.above.horizontal.and.45º.below.horizontal,.which.is.limited.by.the.permanent.stop . . This.stop.
should.not.be.removed . . Additional.stops.can.be.inserted.to.limit.travel.above.and.below.horizontal.according.to.figure.4 . . Factory.
default.stops.are.set.at.45°.above.horizontal.and.45°.below.horizontal . . The.stops.and.plugs.have.a.5/8".hex.head . . If.a.hole.does.not.
have.a.stop,.it.should.have.a.plug .
. . O perating.the.monitor.without.the.permanent.travel.limit.stop.in.place.could.cause.damage.to.the.monitor.and.
could.potentially.injure.the.operator . . The.monitor.is.set.for.+45°.and.-45°.travel.limits.unless.otherwise.requested.
by.the.customer . .
. . . T he.travel.limitstop.is.intended.to.be.a.safety.feature.on.the.monitor.in.the.event.that.the.programmed.soft.
stop.would.fail.to.limit.travel . . Continuous,.repeated.impact.into.the.hard.stop.may.cause.damage.or.failure.to.
the.motor . .
Figure 4 – Elevation Stops
PERMANENT STOP (DO NOT REMOVE)
Nozzle Installation
The.nozzle.should.be.threaded.onto.the.outlet.of.the.monitor . . Position.the.pattern.actuator.in.a.position.that.does.not.stretch.the.
power.cord,.and.then.tighten.the.swivel . . Verify.that.the.actuator.orientation.does.not.interfere.with.the.monitor .
. . E nsure.the.thread.on.the.nozzle.swivel.matches.the.thread.on.the.monitor.outlet . . Do.not.over-tighten.the..
nozzle.onto.the.unit .
. Use.a.nozzle.of.the.same.material.as.the.monitor.to.eliminate.the.effects.of.galvanic.corrosion .
ADJUSTABLE
ROTATION STOP LOCATIONS
ANGLE OF
ROTATION
± 92.5 ~ (STD)
± 137.5°
± 177.5°
A
B
C
D
Page.7
ADJUSTABLE
ELEVATION STOP LOCATIONS
ANGLE OF
STOP LOCATIONS
ELEVATION (UP)
1, 4
+122°
2, 3
+92° (STD)
PERMANENT STOP
+70° (FOAM TUBE MAX)
ONLY
+47°
ANGLE OF
ELEVATION (DOWN)
-22°
122°
-47° (FOAM TUBE MIN)
-72°
92°
72°
47°
22°
E
47°
72°
STOP LOCATIONS
PERMANENT STOP
E
D (FOAM TUBE)
C
STOP LOCATIONS
B
A
PERMANENT STOP