Installation with external air supply
Fig. 12 - Base
Fig. 12 - Pedestal
1. Attach the hose to the external air connector using a
hose clip (NB! Do not fi t a hose clip onto the Jøtul F 483
pedestal with a rotating set as this prevents the set from
rotating). NB! Make sure the hose is long enough so that
joints are not necessary. The external air hose insulation
ends approx. 10 cm below the burn chamber.
2. Refi t any parts that have been removed from the product.
10
4.3 Chimney and fl ue pipe
The fi replace must only be connected to a chimney and
fl ue pipe approved for solid fuel fi replaces with fl ue gas
temperatures as specifi ed in «1.0 Technical Data».
The cross-section of the chimney must be designed to fi t
the fi replace. Use «1.0 Technical Data» to calculate the
correct chimney cross-section.
The chimney must be connected in accordance with the
installation instructions of the chimney supplier.
Before a hole is made in the chimney, the product should
be test-mounted in order to correctly mark the position of
the fi replace and the hole in the chimney. See fi g. 1 for
minimum dimensions.
Make sure that the fl ue pipe rises all the way up to the
chimney.
With a rear outlet, use a fl ue pipe bend with a sweep hatch
to allow sweeping.
Please note that it is extremely important for connections
to have a degree of fl exibility. This is to prevent any
movement in the installation leading to the formation of
cracks.
For recommended chimney draught, see «1.0 Technical
Data». For fl ue pipe dimensions with the relevant cross-
section, see "1.0 Technical Data".
NB! The minimum recommended chimney length is 3.5 m
from the fl ue pipe insert. If the draught is too strong, a fl ue
pipe damper can be installed and used to reduce the draught.