Troubleshooting – Solenoid Valve: Part nos. S07-067 (closed
body) & S07-067A (thru body)
Turn off water supplies to the unit before troubleshooting.
Item
Qty.
Part No.
1
1
118-307
1
1
118-307A
2
1
269-983
3
1
269-577
4
1
269-578
5
1
269-1729
6
1
269-1730
7
1
269-579
8
3
160-447
9
1
125-165
Repair Kit S65-113
Item
Qty.
2
1
3
1
4
1
Problem
Cause
An individual
Debris is
operating
trapped
station fails
between the
to shut off
diaphragm
and drips.
and the valve
seat.
An individual
A failed coil for
operating
the valve or
station fails
loose electrical
to turn on.
connection to
the terminal.
Bradley • 215-1771 Rev. D; ECN 13-08-028
Description
Valve Body, ¼" Closed
Valve Body, ¼" Thru
Diaphram
Armature
Spring
Armature Housing
Clamp, Armature Housing
Coil, Solenoid Valve
Screw, #8 x 5/8
O-Ring, #2-013
Description
Diaphram
Armature
Spring
Remove debris between diaphragm and the valve seat.
1. Remove the three #8 Phillips-head screws that hold the solenoid valve assembly together. Be
careful not to lose the armature or spring.
2. Remove the diaphragm. Remove any particles that have been trapped between the
diaphragm and the valve seat. Rinse off the diaphragm and inspect for damage. Make sure
the center orifice and both small side orifices are open.
3. Reassemble in reverse order (do not overtighten the Phillips-head screws or the plastic valve
body may crack). Tighten until the armature plate makes contact with the plastic body.
4. Reconnect the wiring.
Test the station to determine the cause.
1. Disconnect the wires from the coil of an adjacent valve. Disconnect the wires from the
problem valve and reconnect to the adjacent valve.
2. Turn on electrical and water supplies to the unit. Pass your hand in front of the sensor of the
problem station, and the adjacent station should turn on.
3.
If the adjacent station turns on and cycles normally, replace the coil on the problem valve.
If the adjacent valve fails to turn on, inspect the wires from the sensor cable and do the following:
• make sure there are no breaks and that the fully insulated disconnect terminals are firmly
crimped in place;
• turn off the electrical and water supplies;
• reconnect to the adjacent valve and turn on the water supplies to the unit;
• pass your hand in front of the sensor. If the station still fails to turn on, replace the sensor.
8
7
8
1
9